[Ultra Precise Earth Resistance Measurement] ETCR3000A+ earth resistance meter can measure the range from 0.10Ω to 2000Ω with a resolution of 0.01Ω, making it ideal for critical systems with low resistance. It also accurately measures AC voltages up to 200V with 1V resolution. This equipment is equipped with excellent anti-interference design, ensuring stable performance even under difficult environments.
[Automatic Wire Resistance Correction] Our new technology corrects errors caused by poor test lead contacts or extension cords, ensuring high accuracy in field measurements.
[Auxiliary ground rod determination] The earth tester is equipped with an auxiliary earth rod determination function, which improves the accuracy of ground resistance measurements on site.
[Lightweight and field applicable design] The earth resistance meter is only 470g, and the compact main unit is easy to carry. User-friendly and intuitive operation thanks to the top-mounted interface, vertical hand-held format, and easy rotation knob.
【Durable for Industrial Work】Made of ABS material, the ground resistance meter is durable and moisture-proof, and the device features a backlit LCD display that is easy to read under all light conditions, ensuring reliable performance even in difficult environments.
specification:
Model: ETCR3000A+ Earth resistance meter
Earth resistance:
Range: 0.10Ω to 20Ω, Resolution: 0.01Ω
Range: 0.1Ω to 200Ω, Resolution: 0.1Ω
Range: 1Ω to 2000Ω, Resolution: 1Ω
Earth voltage: Range: AC0V to 200V, Resolution: 1V
Seed: ±2%rdg±3dgt
Power supply: DC9V (6 alkaline batteries LR6 1.5V)
Backlight: Adjustable brightness for use in dimly lit areas
Measurement mode: high precision 3-wire measurement, simple 2-wire measurement
Measurement method:
Earth resistance: rated current variable pole, measurement current 20mA Max;
Voltage: RMS collection
Test frequency: 128Hz
Test current: >20mA (sine wave)
Auxiliary pile determination: Avoid errors caused by excessive grounding resistance of auxiliary grounding electrodes.
Circuit resistance calibration: Avoid errors caused by the test cable not being fully inserted into the equipment connection port, poor contact, or the user replacing the test cable extension, etc.
Body size: 160mm x 100mm x 66mm
Test line: 3 strips: 1 each of red 15m, yellow 10m, green 5m
Simple test line: Red 1.5m
Auxiliary grounding rod: 2 pieces: φ9mm x 230mm
Measurement time:
Voltage to ground: approx. 2 times/sec
Ground resistance: about 15 seconds/times
Number of measurements: 5000 times or more (20Ω gear measurement 10Ω, stop for 30 seconds after one measurement and measure again)
Circuit voltage: Voltage to ground measurement: Measurement at AC200V or less
Working current:
Backlight: 56mA Max
Standby: 20mA Max (backlight off)
Measurement: 200mA Max (backlight off)
Body weight:
Body: Approx. 470g (including battery)
Total weight: Approx. 2000g (including accessories)
Working temperature and humidity: -10℃~40℃, 80%RH or less
Storage temperature and humidity: -20°C to 60°C, 70% rh or less
Overload protection: Earth resistance measurement: AC280V/3 seconds between E-P and E-C ports
Insulation resistance: 10MΩ or more (500V between circuit and housing)
Voltage resistance: AC 3700V/rms (between circuit and enclosure)
Electromagnetic properties: IEC61010-4-3, radio frequency EMF ≤ 1V/m
Product safety standards: IEC61010-1, IEC1010-2-31, IEC61557-1, pollution class 2, CAT III 300V
accessories:
1*Earth resistance meter
1*Tool kit
1*Auxiliary ground rod
1*test cable
1*Simple test lead
1*Japanese instruction manual
*Due to import regulations and customs reasons, this product does not include batteries, so please prepare them in advance
Note: The color of the actual product may differ from the photo due to light.
There may be slight deviations in product measurements.